Power Saver™ Program
Variable Frequency Drives

We provide Variable Frequency Drives (VFD) rebates to Austin Energy customers as part of our Commercial offerings. If you would like to apply for this commercial rebate, please review our rebate information below and email commercialrebates@austinenergy.com.

Rebate Package

Description Offering
Guidelines and Rebate Application
Guidelines
 


Rebate Summary
The following formulas are applied to all VFD retrofits when used with HVAC equipment. The formulas apply to variable air volume air handling units, cooling tower fans, and variable flow primary and secondary chilled water pumps. These formulas only apply to the installation of variable (not constant) torque VFDs. The rebate is calculated at $250 per Direct kW.

Air Handling Units

 If you had Inlet Guide Vane Air Volume Controls:
Direct kW = 0.08 kW/hp x Motor hp
 If you had Outlet Damper Air Volume Controls:
Direct kW = 0.19 kW/hp x Motor hp
 If you had a Constant Volume System with no Air Volume Controls:
Direct kW = 0.13 kW/hp x Motor hp

Cooling Tower Fans

DFex and OFex are the diversity and oversize factors of existing cooling towers. The table below shows the default diversity factors and the formula below shows the oversize factor calculation.

 

Diversity Factor    
Number of Cooling Tower Fan Motors DFex
1 or 2 1.0
2 to 4 0.9
Over 4 0.8
Oversize Factor
[at design conditions, (@97°F DB and 75°F WB)]
  • OFex = Cooling Tower Rated Capacity / [Building Peak Load Tons]
  • Direct kW = 0.62 kW/hp x No. or Fan Motors x Fan Motor hp x [(1/OFex) – (1/OFex)3] x DFex
   

 

HVAC Water Pumps

DFex and OFex are the diversity and oversize factors of the existing secondary chilled water pumping system. The table below shows the default diversity factors and the formula below shows the oversize factor calculation.

 

Diversity Factor

   
Number of Secondary Chilled Water Pumps DFex
1 or 2 1.0
2 to 4 0.9
Over 4 0.8

Oversize Factor
[at design condition, (@97°F DB and 75°F WB)]

  • OFex = Design Water Flow Rate (GPM) / Required Water Flow Rate at Peak Conditions (GPM)
  • Direct kW = 0.62 kW/hp x Pump Motor hp x [1-(1/OFex)3 x DFex
   


Funding
Funding is limited and is available only to Austin Energy customers on a first-come, first-served basis. The offering is subject to change without notice.

Power Saver™ Program — Saving Energy Together

 

 
Links
 
 Qualifications,Guidelines & Rebate Application (pdf)

Related Content
 
Participating Companies
Air Conditioning
Reflective Roof
Chilles
Custom Technologies
Lighting
Energy Recovery Ventilator (ERV)
Motors
Window Treatments
Commercial/Business
Load Co-op
Multi-Family Properties
Power PartnerThermostats
Small Business
Solar Photovoltaics
Thermal Energy Storage

 
    Austin Energy Logo    
© 2012 Austin Energy. All rights reserved.En Español | Site Map |Privacy Statement | City of Austin | Contact Us